Call for Pricing and to Order

Product Description
Features:
* UL listed and FM approved.
* Rugged frame, expanded wrench area.
* Tapered orifice prevents turbulence, provides unifrom distribution throughout all pressures.
* Unique deflector accounts for high degree of water atomization associated with Firematic sprinklers.
* Operates at full volume approximately one-tenth of a second after pressure is released.
Specifications:
* PRINCIPLES OF OPERATION: The glycerin inside the bulb has a higher coefficient of thermal expansion than the glass bulb. Thus, when heated, it expands faster than the glass, causing the glass to shatter. The water pressure then pushes the retainer out of the way.
* LITERATURE: Click Here
* SPECIFICATIONS
o DIMENSIONS
+ Length: 2 1/4"
+ Width: 1 3/4"
+ Orifice: 1/2"
+ Thread: 1/2" NPT
o SET POINT: 155° F
o TEMPERATURE RANGE: -40° F to100° F
o TEXT: Note:The bulb does not suffer any ill effects from cold temperatures - the glycerin inside will not allow the bulb to freeze. If one activates in cold weather, it's most likely due to the high pressures that result from water freezing in a fixed volume (e.g., the pipe).
o COVERAGE: 10' x10'
o BULB LIQUID: Glycerin
o K FACTOR: 5.6
o RELATED PARTS: Use only Firematic and Globe sprinkler wrenches SPWR , RSW2